- Insulation resistance measurement:
- selected test voltage: any voltage in the 50...1000V range with 10V step,
- automatic measurement in sockets with the UNI-Schuko adapter with possibility of configuring pairs of measured cables,
- continuous indication of insulation resistance or leakage current,
- automatic discharge of capacitance of tested object after the insulation resistance measurement,
- acoustic signalling of five-second periods to facilitate obtaining time characteristics,
- measured test times T1, T2 i T3 to measure one or two absorption coefficients in the 1... 600 sec. range,
- indication of actual test voltage during the measurement,
- protection against measuring live objects,
- three-lead measurement. - Continuity measurement of protective and equipotential conductors according to EN 61557-4 with the >200mA current
- Low-voltage circuit continuity and resistance measurement:
- circuit resistance measurement (<1999 ) with the <15mA current,
- quick sound signal if circuit resistance is below 30. - Leakage current measurement.
- Capacitance measurement during the RISO measurement
- Measurement of alternating and direct voltages in the 0...600V range.
- 990 memory cells and wireless data transmission to a computer using the USB - OR-1 adapted.
- Power supply: 4 AA disposable or rechargeable batteries, monitoring of power supply voltage.
- Meters conform to EN 61557.